Heating flow is load divided by the product of fluid heat capacity and design temperature drop. In US water practice installers often use the shorthand GPM ≈ BTU/h ÷ (500 × ΔT°F) for water near room conditions. Metric work uses kW and Kelvin the same way with the matching constant.
Pick ΔT before you trust GPM
- 20°F (about 11K): common boiler design ΔT on many residential jobs.
- 10K / 5K: heat pump and low-temp loops often run cooler spreads, which raises required flow. See heat pump ΔT.
On the job
- Confirm load units (BTU/h vs kW).
- Confirm design ΔT and fluid (water vs glycol).
- Compute flow, then open Hydronic Calculator Flow to cross-check with live US/metric switch.
- Use the GPM checklist before you pipe off that number.
For qualified installers. Always verify results against local codes and manufacturer data.