Duty point checks before you pick a circulator

Prep the duty point, then read the OEM curve. The app does not replace manufacturer curves.

Circulator with abstract duty-point curve
  1. Required flow from the heat load (Flow mode).
  2. Pipe size and material from Pipe mode or drawings.
  3. Equivalent length including fittings.
  4. Fluid (water or glycol percent).
  5. Compute required head / duty point in Pro Circulator.
  6. Open the manufacturer pump curve for the candidate model.
  7. Confirm the duty point sits on a sensible curve region (not only max speed marketing).
  8. Recheck if zone valves or bypasses change the circuit.

Pipe background: pipe sizing guide.